Laserfiche WebLink
ATTY/RESO.0091/PC RESO APPROVING THE PC PERMIT & TM - PHASE 1 STANFORD <br />REV: 09-29-16 JS <br />Page 13 of 15 <br /> <br />system, the application of 13D systems is one and two family dwellings only). Revise the notation under deferred submittals to indicate that the fire sprinkler system will be a combination sprinkler/standpipe system with hose connections on all levels of the building (CFC Section 905). [SDR][FIRE] <br />58. Fire Department Access Plan – Provide a fire department access plan that indicates all routes of fire department road access required to within 150 feet of all portions of the exterior of the building unless otherwise approved by the Redwood City Fire Department (CFC Section 503). <br />59. Premises Identification (Address Numbers) – Indicate on the plans where the premises identification (address) will be located and the size (minimum 12 inches) in a contrast background facing the street from which the building takes the address (CFC Section 505). The following requirements also apply: [COA][FIRE] <br />a. Addresses must be logical, sequential numbers, i.e. First Floor 101, 102, 103, Second Floor 202, 203, 204, as opposed to F303, G401, etc. <br />b. Floor plan maps shall be submitted with unit numbers at all entrances, excluding fire exits. <br />c. Provide a key pad with 24 hour access code for public safety personnel at the main entrance, as opposed to just RFID readers or similar devices. <br />60. Elevator Requirements – The following requirements for elevators apply: [SDR][BUILDING] <br />a. One elevator shall be available for use as an accessible means of egress in case of emergency. <br />b. One elevator shall be connected to backup generator power in order to remain operable during emergencies. This elevator shall be provided with appropriate signage and shall extend to all floors including the lower levels of the parking structure <br />c. All additional elevators shall be connected to battery backup with sufficient power to bring the elevator to the exit level in the event of an emergency. <br />d. All elevators shall be equipped with smoke curtains. <br />e. Elevators in buildings that are four or more stories shall accommodate an ambulance stretcher and all associated requirements per CBC 3002.4. [SDR][FIRE] Construction-Related Activities <br />61. Verification for Dimensions – All dimensions, including building location on the site, setbacks, building height, etc. shall be verified by a licensed surveyor. A survey report shall be provided to the Building Inspector for review and approval. [COA][BUILDING] <br />62. Sales and Use Taxes – Applicant shall use good faith efforts to register with the Board of Equalization to create an ID prior to project construction and operation. This maximizes the City’s allocation of sales and use taxes associated with project construction. Contact Nancy Murguia, Finance Department, at (650) 780-7097 or nmurguia@redwoodcity.org. [DA][FINANCE] <br />63. Hours of Construction – On-site construction activity is permitted between 7:00 a.m. and 8:00 p.m. Monday through Friday, except as permitted on weekends by the Building Official, and shall adhere to the City’s Noise Ordinance. If possible, the noisiest construction activities would be scheduled for daytime hours when the ambient noise levels are highest. [SDR][BUILDING] <br />64. Construction Meetings – The applicant is required to contact the Permit Counter (650.780.7350) to schedule the following meetings prior to or during construction. [COA][BUILDING]