Laserfiche WebLink
<br /> FXS:dft - ]/92 (009/11) <br /> 9/14/92R <br />line of sight to an outside exit door, or (b) when <br />required by the Electrical Inspector or Fire Marshal." <br />"Section 9.114. Section 300-22(e) of the Electrical <br />Code is hereby amended to read as follows: <br /> "'Section 300-22(e). Low Voltage Wiring Above <br />Suspended Ceilings. Low voltage and communication <br />system wiring ins tailed above suspended ceilings shall <br />be: <br /> "'(1) Installed with approved straps or hangers. <br /> "'(2) Protected from possible damage. <br /> "'(3) A minimum of twelve (12) inches above the <br /> suspended ceiling. If the suspended ceiling is <br /> installed with less than (12 ) inch clearance to <br /> the structure above, such wiring shall be <br /> installed so that all ceiling tiles can be <br /> removed. <br /> '" (4) Installed in accordance with any other more <br /> restrictive codes or installation instructions. '" <br />"Section 9.115. Section 310-2(b) of the Electrical <br />Code is hereby amended to read as follows: <br /> "'Section 310-2(b). Conductors. Conductor sizes <br />smaller than No. 2 shall be of copper. Conductors No. <br />2 and larger may be of aluminum, copper-clad aluminum, <br />or copper unless otherwise specified." <br />SECTION 7. Division 2 of Article IX of Chapter 9 of the <br />Redwood City Code is hereby added to read as follows: <br />"DIVISION 2. AREAS OF REDWOOD CITY UNDERLAIN <br /> BY YOUNGER BAY MUD <br />Sections 9.121 through 9.131 are hereby deleted and replaced <br />by the following: <br /> 15 <br />- <br />