Laserfiche WebLink
<br /> MSR:dp:8/28/78R <br />shall be installed and maintained in accordance with <br />the Safety Orders of the State Division of Industrial <br />Safety and subject to the approval of the Chief. These <br />orders shall apply to all persons and placed within the <br />municipality except as herein provided. <br />" , (d) containers shall be located with respect to <br />buildings or line of adjoining property which may be <br />built upon in accordance with the following table: <br /> TABLE 20.105 <br />CONTAINER CAPACITY MINIMUM DISTANCE <br />Less than 100 gallons 5 feet <br />100 to 500 gallons 10 feet <br />501 to 1200 gallons 25 feet <br />Over 1200 gallons 50 feet <br />NOTE: At the discretion of the Chief, containers <br /> may be located a lesser distance to buildings <br /> of not less than one hour construction, <br /> provided the above distances applied to <br /> openings in buildings are maintained, and <br /> the relief valves will not discharge in the <br /> direction of a means of egress or against <br /> the buildings. <br />" , (e) No stationary storage tank shall be less than <br />ten feet from the nearest street line or sidewalk. , <br />"Section 12.19 Section 27.105 of the Fire Code is hereby <br />amended to read as follows: <br />"'Section 27.105 TYPES AND CONSTRUCTION OF INCINERATORS. <br />" , (a) Every incinerator used shall comply with the <br />provisions of this Section. <br />" , (b) Commercial, industrial and apartment type <br />incinerators shall be constructed in accordance with the <br />provisions of the Building and Mechanical Codes. <br /> -21- <br /> .....-..-. ..- <br />