<br />"Section 12.20 <br /> <br />Section 15.216 of the Fire Code is <br /> <br />hereby amended to read as follows: <br />"ISection 15.216 TESTING. <br />" 'a. Before being covered or placed in use, all <br />tanks and that piping which is in a suction system shall <br />be tested hydrostatically or with air pressure at not <br />less than three pounds per square inch gauge, nor more <br />than five pounds per square inch gauge. Pressure piping <br />shall be tested to 150 per cent of the working pressure <br />or 75 pounds per square inch gauge whichever is greater. <br />Tests shQll be maintained for at least 30 minutes and <br />shall be witnessed by a Fire Inspector. <br />"lb. The pipe system between the pump and dispenser, <br />but not including the pump, tank or thri dispenser, shall <br />be tested hydrostatically for 30 minutes to 150 per cent <br />of the shut-off pressure of the pump or 75 pounds per <br />square inch gauge, \",hichever is greater, to insure <br />tightness. The test liquid shall be that for which <br />the system is intended.' <br />"Section 12.21 Section 15.305 of the Fire Code is <br />hereby amended to read as follows: <br />"Section 15.305 SWING JOINT'S.. Underground <br />piping shall incorporate swing joints at the points <br />where such piping leaves the dispensi~g l~cation and _ <br />at the point of connection to tank fittings. Additional <br />swing joints may be required as determined by the Chief.1 <br />"section 12.22 Section 15.306 is hereby add(~d to <br />Division III of Article 15 of the Fire Code to read as <br />follows: <br /> <br />"'Section 15.306 <br /> <br />JOINTS AND CO~mECTIONS. All <br /> <br />-20- <br /> <br />or <br />