05/20/2019 <br />system needs to be a campus -wide system with one set of bi-directional amplifiers with <br />coverage extended into all levels of all buildings and garages. This signal distribution is typically <br />accomplished with fiber optics. [COA] [FIRE] <br />55. Fire Department Knox Building Access - Knox Key boxes are required as part of this project <br />to allow emergency access for firefighters to all buildings. Indicate on the pains that Knox Key <br />boxes will be provided at the entrances to all buildings at locations approved by the fire <br />department. Recessed key boxes shall be installed at all buildings five to six feet above finished <br />grade. [SDR- CFC 506][FIRE] <br />56. Fire Apparatus Turn Arounds - Are required at the end of all Fire Access Lanes in excess of <br />150 feet. These turnarounds shall meet the City of Redwood City engineering standards. [SDR - <br />D103.4] [FIRE] <br />57. Access Roads - Fire apparatus access roads shall be designed and maintained to support the <br />imposed loads of fire apparatus and shall be surfaced so as to provide all weather driving <br />capabilities. Fire access lanes shall be engineered to carry the imposed load of 75,000 pounds <br />and be surfaced with AC or Concrete. Concrete may be stamped or pervious as long as it meets <br />the load bearing requirements. [SDR -503.2.3] [FIRE] <br />58. Aerial Apparatus - At least one of the required aerial fire apparatus access routes meeting this <br />condition shall be located within a minimum of 15 feet and a maximum of 30 feet from each <br />building, and shall be positioned parallel to one entire side of each building as per 2016 CFC <br />D105.3. [FIRE] <br />59. No Parking -The plans indicate a number of Red Curb fire lane designations. In addition to red <br />curbs, appropriate Fire Lane No Parking signs are required as per Appendix D of the CFC. [FIRE] <br />60. Atrium Smoke Removal System - The plans indicate a three story Atrium in one of the <br />buildings. Provide engineered plans and air handling calculations for the required smoke <br />removal system for the Atrium. [FIRE] <br />61. Available Water Supply to Project Site - Provide current fire flow information from the water <br />purveyor to indicate the maximum available water flow in gallons per minute (GPM) at a <br />minimum of 20 pounds per square inch (psi) residual pressure. This Information must be dated <br />and indicate the information is the most current information available from the water <br />purveyor. [FIRE] <br />62. Automatic Fire Sprinkler / Standpipe Systems Required - As the proposed buildings are <br />four or more stories in height, all of the buildings and garage areas are required to be equipped <br />with automatic standpipe / fire sprinkler systems. Provide plans and hydraulic calculations for <br />the design of these systems. The plans for these systems shall include on-site exterior standpipe <br />connections and interior standpipe connections in all of the buildings stairwells that need to be <br />included in the hydraulic calculations. The plans indicate a number of exterior standpipe <br />connections around the campus. The fire pumps supplying these standpipe connections are <br />required to be sized to provide the required total 1000 GPM flow at 125 Psi at the highest <br />elevation standpipe connections. [FIRE] <br />63. Fire Department Connections - FDC's to the fire sprinkler / standpipe systems shall be <br />located at the fire access side of all buildings within 50 feet of a Fire Hydrant. [FIRE] <br />ArFY/RESO.0051 CC RESO APPROVING PROJECT— BROADWAY PLAZA RESO. NO. 15769 <br />REV: 05-15-19 PR MUFF NO. 601 <br />Page 1S of 22 <br />