Laserfiche WebLink
8.13. - Page 37 of 63 <br />C. Stand Alone Cooking Oven <br />1. A dedicated 208/240 -volt, 20 -amp or greater or greater receptacle within 3 <br />feet of the appliance and accessible with no obstructions; <br />2. Both ends of the unused conductor shall be labeled with the words "For <br />Future Convection Oven" and be electrically isolated; <br />3. A double pole circuit breaker in the electrical panel labeled with the words <br />"For Future Electric Oven;" and <br />4. Other electrical components, including conductors, receptacles or blank <br />covers, related to this section shall be installed in accordance with the <br />California Electrical Code. <br />Sec. 9.229. - SECTION 150.1(B) OF THE ENERGY CODE AMENDED: <br />Section 150.1(b) of the Energy Code is amended to read as follows: <br />(b) Performance Standards. A building complies with the performance standards if <br />the energy consumption for the Proposed Design Building is no greater than the <br />energy budget calculated for the Standard Design Building using Commission - <br />certified compliance software as specified by the Alternative Calculation Methods <br />Approval Manual. Mixed -Fuel Buildings must additional reach an EDR margin above <br />the Standard Design in order to comply with performance standards. <br />Sec. 9.230. - SECTION 150.1(B) 1 OF THE ENERGY CODE AMENDED: <br />Section 150.1(b) 1 of the Energy Code is amended to read as follows: <br />1. Newly Constructed Buildings. The Energy Budget for newly constructed <br />buildings is expressed in terms of the Energy Design Rating, which is based on <br />TDV energy. The Energy Design Rating (EDR) has two components, the <br />Energy Efficiency Design Rating, and the Solar Electric Generation and <br />Demand Flexibility Design Rating. The Solar Electric Generation and Demand <br />Flexibility Design Rating shall be subtracted from the Energy Efficiency Design <br />Rating to determine the Total Energy Design Rating. The Proposed Building <br />shall separately comply with the Energy Efficiency Design Rating and the Total <br />Energy Design Rating in the following ways: <br />A. All -Electric Building. All Electric Buildings comply if both the Total Energy <br />Design Rating and the Energy Efficiency Design Rating for the Proposed <br />Building are no greater than the corresponding Energy Design Ratings for <br />the Standard (Baseline) Design Building. <br />B. Free Standing Accessory Dwelling Unit. Free Standing Accessory Dwelling <br />Units comply if both the Total Energy Design Rating and the Energy <br />Efficiency Design Rating for the Proposed Building are no greater than the <br />corresponding Energy Design Ratings for the Standard (Baseline) Design <br />Building. <br />C. Mixed -Fuel Buildings: A Mixed -fuel single-family or multifamily building <br />complies with the performance standards if the Energy Efficiency Design <br />Rating of the Proposed Building is no greater than the Energy Efficiency <br />ATTY/ORD.504/CC ORDINANCE ADDING CALIFORNIA ENERGY CODE & GREEN BUILDING STANDARDS <br />REV: 10-24-19 RL <br />Page 9 of 18 <br />181 <br />