Laserfiche WebLink
7.A. - Page 191 of 285 2019 Nonresidential New Construction Reach Code Cost Effectiveness Study <br />the battery comes from a renewable source. Thus, the Reach Code Team also applied a 19 percent cost <br />reduction to battery costs. <br />3.2.3 PV -only and PV+Battery Packages <br />The Reach Code Team analyzed solar PV and battery storage only, without other efficiency measures in <br />both mixed -fuel and all -electric building designs. Two different sizes of solar PV and battery storage were <br />analyzed. <br />♦ Small PV Size: 3 kW, assumed to be the minimal PV system considered for installation in a <br />nonresidential building. <br />♦ Large PV Size: PV capacity equal to 15 W/ft2 over 50 percent of the roof area, or sized to nearly <br />offset annual electricity consumption, as described in Section 3.2.1. <br />♦ Small Battery Size: 5 kWh, assumed to be the minimal battery system considered for installation <br />in a nonresidential building, and representative of smaller products currently available on the <br />market. <br />♦ Large Battery Size: 50 kWh, assumed to be a substantially large size for a nonresidential setting. <br />Generally, the reach code team found diminishing on -bill and TDV benefits as the battery size <br />increased. <br />As described in Section 1 and Section 4.4, each PV size was run as a standalone measure. When packaged <br />with a battery measure, the small PV size was paired with the small battery size, and the large PV size was <br />paired with the large battery size. <br />3.3 All Electric Measures <br />The Reach Code Team investigated the cost and performance impacts and associated infrastructure costs <br />associated with changing the baseline HVAC and water heating systems to all -electric equipment. This <br />includes heat pump space heating, electric resistance reheat coils, electric water heater with storage tank, <br />heat pump water heating, increasing electrical capacity, and eliminating natural gas connections that <br />would have been present in mixed -fuel new construction. The Reach Code Team selected electric systems <br />that would be installed instead of gas -fueled systems in each prototype. <br />3.3.1 HVAC and Water Heating <br />The nonresidential standards use a mixed -fuel baseline for the Standard Design systems. In most <br />nonresidential occupancies, the baseline is natural gas space heating. Hotel/motels and high-rise <br />residential occupancies also assume natural gas baseline water heating systems for the guest rooms and <br />dwelling units. In the all -electric scenario, gas equipment serving these end -uses is replaced with electric <br />equipment, as described in Figure 9. <br />16 <br />RE <br />2019-07-25 <br />443 <br />