Laserfiche WebLink
6.1.E. - Page 26 <br />Attachment 1 <br />Peninsula Humane Society Building Deficiencies Survey: April 8, 2011 <br />Consideration taken into account for occupancy of 5 to 8 years maximum. <br />1. Outside Drainage: <br />Although it was not raining, nor, had it rained for several days prior to our walkthrough, <br />large amounts of standing water were evident. I was informed that the parking lot and <br />rear of the building flood frequently during storms, and, that the surface drains did not <br />work. It was also noted that the County Parks Dept. would not allow clean out service to <br />be performed where the storm drains 'Day Light' to the bay. During the outside <br />inspection, it was also obvious that the grade sloped toward the building structure <br />causing flooding into the facility. <br />2. Exterior Siding and Paint: <br />Structurally, the exterior siding of the building will hold up for the occupancy <br />requirement with minimum repairs. Unfortunately, it would still remain cosmetically <br />unappealing in some areas. <br />The exterior siding and trim will, however, need to be painted in order to last without <br />failure for next 5 to 8 years. <br />3. Roof: <br />Approximately 70% of the flat roof areas appear to be original from when constructed. I <br />would recommend a roofing consultant be contacted to inspect these areas to <br />determine if the roof will last 5 to 8 years. The other 30% of the flat roof is new within <br />the last 5 years and will not require replacement, particularly over the Spay /Neuter <br />area. The pitch roof areas are composition shingles and appear to be satisfactory, <br />however, there is a major leak under a pitch roof /clear story area that will need to be <br />found and repaired. <br />4. Life Safety System: <br />I was advised by Ken White that the Fire Alarm system was compliant per the Fire <br />Marshall, however, I would advise reconfirmation. <br />S. ADA: <br />Entire facility - Not Compliant i.e. Manual front doors, restrooms not sufficient size, etc. <br />ATTY/AGR/201 1 /AMEN DM ENTS/AMEN D NO.3 ANIMAL CONTORL <br />060711 - 23 - <br />