Laserfiche WebLink
Proposed Senior Assisted Living Facility <br /> PSI Project No. 575-308-2 <br /> August 3, 2011 <br /> Page 12 <br /> inches below and 12 inches above the pipe for the full trench width. The bedding material <br /> should be mechanically compacted in layers to at least 90 percent of maximum dry density <br /> based on ASTM D1557. Flooding should not be permitted. <br /> Trench backfill above pipe bedding should consist of approved on-site or import soils placed in <br /> lifts no greater than 8 inches loose thickness, moisture conditioned as per our recommendations <br /> for fill soils, and compacted to minimum 90 percent of the maximum dry density per ASTM <br /> D1557. Some minor settlement of the backfill should be expected and any utilities within the <br /> trenches or concrete walks supported on the trench backfill should be designed to accept these <br /> differential movements. <br /> Except where extending perpendicular under proposed foundations, utility trenches should be <br /> constructed outside a 1:1 projection from the base-of-foundations. Trench excavations for utility <br /> lines, which extend under structural areas should be properly backfilled and compacted. <br /> 5.4 Foundation Support <br /> Following site preparation, as recommended in Section 5.1, it is our opinion that conventional <br /> continuous strip or isolated footings supported by low expansive Engineered Fill are suitable for <br /> the support of the proposed structure. The perimeter footings should have a minimum depth of <br /> 18 inches below the lowest adjacent grade, with a minimum width of 18 inches. Column <br /> footings should have a minimum depth of 18 inches below the lowest adjacent grade, with a <br /> minimum width of 24 inches. Footings with the above recommended minimum dimensions may <br /> be designed for an allowable soil bearing pressure of 2,500 psf. The allowable soil bearing <br /> pressure can be increased by one-third for short-term wind or seismic load considerations. <br /> Based on the estimated liquefaction-induced settlements, we recommend that all strip footings <br /> be longitudinally reinforced with at least 4 No. 4 bars (two top and two bottom). This steel <br /> reinforcement is not intended to be used in lieu of that needed for structural considerations but <br /> is recommended due to site geologic conditions. The actual foundation reinforcement and <br /> foundation dimensions should be provided in accordance with the Structural Engineer's design. <br /> Lateral loads may be resisted by any rational method, which incorporates sliding friction and/or <br /> passive earth pressure. The design may incorporate an allowable passive earth pressure of <br /> 250 psf per foot of depth below a depth of 1 foot, provided that the footing concrete is poured <br /> tightly against firm native soil or properly compacted fill materials. This value may be increased <br /> by 250 psf for each additional foot of depth, to a maximum of 2,000 psf. An allowable friction <br /> coefficient of 0.35 may be used at the concrete-soil interface. No reductions are necessary <br /> when combining the frictional and passive resistance of the soils to determine the total lateral <br /> resistance. <br /> We estimate that foundations designed and constructed in accordance with the above <br /> recommendations will experience total static settlements of less than 1-inch with differential <br /> settlements of '/2-inch over a 40 foot span. While settlement of this magnitude is generally <br /> considered tolerable for structures of the type proposed, the design of masonry walls should <br />