Laserfiche WebLink
<br /> S\ ~nt 12/17/87 (#06) <br /> SWC:nt 12/22/87R <br /> device to operate the main swi tch or circuit breaker. The <br /> shunt trip push button device shall be installed (a) where <br /> the main disconnects are more than ten (10) feet of a direct <br /> line of sight to an outside main door, or (b) when required <br /> by the Electrical Inspector or Fire Marshal. II <br /> IISection 9.119. Section 300-22(e) is hereby added to <br /> the Electrical Code to read as follows: <br /> "'Section 300-22(e). Low Voltage Wiring Above <br /> Suspended Ceilings. Low voltage and communication <br /> system wiring installed above suspended ceilings shall <br /> comply with the following requirements: <br /> " , (1) Installed with approved straps or hangers. <br /> '" (2) Protected from possible damage. <br /> II , (3) Maintain a minimum twelve (12) inch <br /> clearance above the suspended ceiling. If the <br /> suspended ceiling is installed with less than (12) <br /> inch clearance to the structure above, such wiring <br /> shall be installed so that all ceiling tiles can <br /> be removed. <br /> II , (4) Installed in accordance with other more <br /> restrictive codes or installation instructions. 'II <br /> SECTION 7. This ordinance shall be effective 30 days after <br /> its adoption. <br /> * * * * <br /> 25 <br />