Laserfiche WebLink
The inlet and outlet connections shall be made by the use of a flexible <br /> compression joint no closer than twelve (12) inches (0.3 m) to, and not farther <br /> than three (3) feet (0.9 m) from the manhole. No flexible compression joints <br /> shall be embedded in the manhole base. <br /> "Section 719.7. Cleanouts shall be installed at the property line where <br /> the private sewer system connects to the publicly-maintained sanitary sewer <br /> lateral. All such line cleanouts shall be extended to grade with materials and <br /> according to specifications approved by the Administrative Authority and <br /> terminate within a concrete box." <br /> "Section 9.88. Section 807.2 of the Plumbing Code is amended to read <br /> as follows: <br /> "Section 807.2. Condensate from air-cooling coils and comfort cooling <br /> equipment not intended to be used for the storage or holding of food or drinks <br /> shall be collected and discharged to a storm sewer or other approved points of <br /> disposal acceptable to the Administrative Authority. <br /> Termination of such drains shall be made by an air break. Condensate <br /> drain lines in sizes 1 1/4" and larger shall be assembled using approved <br /> drainage pipe and fittings. Condensate wastewater shall not drain over or upon <br /> a public way, sidewalk, pedestrian ramp or the like. Condensate drains within <br /> the interior of a building shall not be connected to the building roof drain or <br /> overflow piping systems. The waste pipe shall have a slope of not less than 1/8 <br /> ORD-001 22 <br /> FXS:rg <br /> 10/23/95 <br /> 11/13/95R <br />