Laserfiche WebLink
<br /> - -- <br /> "'Section l2.l3 Section lO.301.l is hereby added to the Fire Coòe <br /> to read as follows: <br /> "'Section lO.30l.l APPROVED AUTOMATIC SPRINKLER SYSTEMS <br /> " , (a) Approved automatic sprinkler systems are integrated <br /> systems of underground and overhead piping including a water <br /> supply of a type such as a gravity tank, fire pump, reservoir or <br /> pressure tank or a connection, by underground piping, to a City <br /> main, and which comply in all respects with the requirements <br /> adopted for such systems as described in the National Fire <br /> Protection Association, Pamphlet No. l3, as it now exists or as <br /> it may from time to time be amended.' <br /> " , (b) Approved automatic sprinkler systems with more than 20 <br /> sprinkler heads shall include a water flow detecting device, and <br /> valves controlling such systems, excepting underground gate <br /> valves with roadway boxes, shall be supervised open by a <br /> monitoring device or devices. Waterflow and monitoring devices <br /> shall operate on a continuous basis to provide immediate <br /> notification of any activation of such systems to a central <br /> station as described in the National Fire Protection <br /> Association, Pamphlet No. 7l, as it now exists or as it may from <br /> time to time be amended.' <br /> -11- <br /> ..-...... <br />