7.A. - Page 194 of 285 2019 Nonresidential New Construction Reach Code Cost Effectiveness Study
<br />Figure 11. Medium Retail HVAC System Costs
<br />Climate Zone
<br />Mixed Fuel
<br />Baseline
<br />All Electric System
<br />Incremental cost
<br />for All -Electric
<br />CZ01
<br />$328,312
<br />$333,291
<br />$4,978
<br />CZ02
<br />$373,139
<br />$373,702
<br />$563
<br />CZ03
<br />$322,849
<br />$326,764
<br />$3,915
<br />CZ04
<br />$329,900
<br />$335,031
<br />$5,131
<br />CZ05
<br />$359,888
<br />$362,408
<br />$2,520
<br />CZ06
<br />$335,728
<br />$341,992
<br />$6,265
<br />CZ07
<br />$345,544
<br />$349,808
<br />$4,265
<br />CZ08
<br />$368,687
<br />$369,792
<br />$1,104
<br />CZ09
<br />$415,155
<br />$411,069
<br />$(4,087)
<br />CZ10
<br />$345,993
<br />$346,748
<br />$755
<br />CZ11
<br />$418,721
<br />$414,546
<br />$(4,175)
<br />CZ12
<br />$405,110
<br />$400,632
<br />$(4,477)
<br />CZ13
<br />$376,003
<br />$375,872
<br />$(131)
<br />CZ14
<br />$405,381
<br />$406,752
<br />$1,371
<br />CZ15
<br />$429,123
<br />$427,606
<br />$(1,517)
<br />CZ16
<br />$401,892
<br />$404,147
<br />$2,256
<br />3.3.1.3 Small Hotel
<br />The small hotel has two different baseline equipment systems, one for the nonresidential spaces and one
<br />for the guest rooms. The nonresidential HVAC system includes two gas hot water boilers, four packaged
<br />rooftop units and twelve VAV terminal boxes with hot water reheat coil. The SHW design includes a small
<br />electric water heater with storage tank. The residential HVAC design includes one single zone AC unit with
<br />gas furnace for each guest room and the water heating design includes one central gas storage water
<br />heater with a recirculation pump for all guest rooms.
<br />For the small hotel all -electric design, the Reach Code Team assumed the nonresidential HVAC system to
<br />be packaged heat pumps with electric resistance VAV terminal units, and the SHW system to remain a
<br />small electric resistance water heater.
<br />For the guest room all -electric HVAC system, the analysis used a single zone (packaged terminal) heat
<br />pump and a central heat pump water heater serving all guest rooms. Central heat pump water heating
<br />with recirculation serving guest rooms cannot yet be modeled in CBECC-Com, and energy impacts were
<br />modeled by simulating individual heat pump water heaters in each guest room. The reach code team
<br />believes this is a conservative assumption, since individual heat pump water heaters will have much
<br />higher tank standby losses. The Reach Code Team attained costs for central heat pump water heating
<br />installation including storage tanks and controls and used these costs in the study.
<br />Cost data for small hotel designs are presented in Figure 12. The all -electric design presents substantial
<br />cost savings because there is no hot water plant or piping distribution system serving the nonresidential
<br />spaces, as well as the lower cost of packaged terminal heat pumps serving the residential spaces
<br />compared to split DX/furnace systems with individual flues.