Laserfiche WebLink
ATTY/RESO.0034/CC RESO APPROVING PROJECT (901 EL CAMINO REAL) – EXHIBIT A <br />REV: 04-22-25 VR <br />Page 18 of 28 <br />shall have the standpipe system extended to the roof level on which the rooftop garden or <br />landscaped roof is located. [FIRE] [CFC §905.3.8] <br /> <br />78. Fire Pump - Emergency Power Source - Electrically driven fire pumps must be provided with <br />an alternate power source in accordance with NFPA 20, Fire Pumps, due to foreseeable <br />extended electrical service interruptions along the California Power Grid. [FIRE] [CFC <br />§913.2.3 and Redwood City Code of Ordinances §12.19] <br /> <br />79. Standby and Emergency Power - A standby power system complying with CBC Section 2702 <br />for emergency power systems and standby power systems, and CBC Section 3003 for <br />standby power for emergency elevator operations, must be provided for the standby power <br />loads specified in CBC Section 403.4.8.3. [FIRE] [CBC §403.4.8] <br /> <br />80. Generator - Standby and Emergency Power – Equipment Room - When a generator is set <br />inside the building for the standby or emergency power systems, the generator shall be <br />located in a separate room enclosed with 2-hour fire barriers. [CBC §403.4.8.1] System <br />supervision with manual start and transfer features must also be provided at the fire <br />command center. [FIRE] <br /> <br />81. Public Safety Key Boxes - Public safety key boxes shall be installed adjacent to each <br />entrance within 60 to 72 inches of the finished walking surface. [CFC §506] The Applicant <br />shall have the key box locations shown on the building permit plans. [FIRE] <br /> <br />82. Public Address System - In buildings four (4) or more stories in height, a public address <br />system shall be installed for the exclusive use of Fire Department personnel, peace officers, <br />or other City enforcement personnel according to specifications approved by the Redwood <br />City Fire Prevention Bureau. The controls for, and access to, such system must be installed <br />on the ground floor of the building at a location subject to the approval of the fire code <br />official. [FIRE] [Redwood City Code of Ordinances §12.23 – 907.2.12.3.1(c) <br /> <br />83. Fire Equipment Enclosure - Buildings of four (4) or more stories in height, a secure cabinet <br />or other enclosed area must be provided for housing fire equipment. Fire equipment <br />required to be provided at the direction of the Fire Code Official. [FIRE] [Redwood City Code <br />of Ordinances §12.23 – 907.2.12.3.1(d)] <br /> <br />84. Emergency Responder Radio Coverage - Emergency responder radio coverage is required <br />based upon the existing coverage levels of the public safety communication systems of the <br />jurisdiction at the exterior of the building. [FIRE] <br /> <br />85. Elevator Car to Accommodate Ambulance Stretcher - Where elevators are provided in <br />buildings four or more stories above grade plane, not fewer than one elevator must be <br />provided for fire department emergency access to all floors. The elevator car shall be of <br />such a size and arrangement to accommodate an ambulance stretcher 24-inches by 84- <br />inches with not less than 5-inch radius corners, in the horizontal, open position and shall be